| |
% of Ampere Rating | Blow Time |
100% | 4 hours, Minimum |
135% | 1 hours, Maximum |
200% | 3 sec Min.; 20 seconds Maximum |
500% | 100 msec Min.; 1.5 seconds Maximum |
1000% | 30 msec Min.; 300 seconds Maximum |
| |
| | |
Interrupting rating | Power Factor | Intended Application |
10,000A, AC@ 125V | 0.7 - 0.8 | General Purpose |
200A, AC@ 250V | 0.7 - 0.8 | Primary Protection |
100A, AC@ 350V | Resistive | Ballast Protection |
60A, AC@ 600V | Resistive | Telecom Protection |
| | |
Ampere Ratings : | | 100mA, 125mA, 160mA, 200mA, 250mA, 300mA, 350mA, 400mA, 500mA, 600mA, 700mA, 750mA, 1A, 1.25A, 1.5A, 2A, 2.5A, 3A, 4A, 5A |
|